KSO switchgear cells -292 (Factory-assembled switchgear cells of one-sided maintenance) are installed in switchgear enclosures and are unilateral maintenance switchgear cells. The configuration is based on diagrams of primary connections. The factory manufactures KSO switchgear cells of Series 200: KSO-202, 203, 205, 206, 266, 272, 285, 292, 298, 299, and 299M.

KSO switchgear cells include installed high-voltage devices of primary circuits: oil-circuit breakers (VMP or VPM) or vacuum load-break switches (bb/tel and VBSK); disconnecting switches (indoor DS with grounding blades or indoor DS with molded insulating bushings and with grounding blades); current and voltage transformers; light-duty valve arresters (RVO), surge protection devices (SPDs); automatics relay; instrumentation; meters; microprocessor units and other devices, depending on diagrams and configuration data sheets.

KSO switchgear cells can be used in the following operating conditions:

- climatic characteristics correspond to cold-temperate climates, category 3 or 4 according to GOST 15150-69;

  - lowest ambient temperature is 1° (for KSO cells without heating systems for meters) and minus 25°С (for KSO switchgear cells equipped with heating systems for meters);

 - highest and effective ambient temperatures are plus 40°С or plus 35°С, respectively;

 - altitude - max 1000 m;

 -non-explosive environment free of current-conducting dust, aggressive gases or vapors damaging metals and insulation.               

          KSO switchgear cells come as a metal structure welded from formed sections. Devices for primary circuits are installed inside; the façade includes the breaker and disconnecting switch mechanism as well as auxiliary circuit devices. The access to the chamber is available through two doors: the upper door leads to the breaker, voltage transformer or fuse areas; the lower door provides access to cable connections, power transformer or discharge switches. The inner side of the door has protection shield that separates devices of auxiliary circuits from the high-voltage area. The cell has inspection ports to monitor the inside part of the cell.

               KSO switchgear cells have an interior lamp fixture that makes it possible to replace safely a burnt-out lamp, without removal of voltage.  Bus bars of KSO switchgear cells are enclosed with a cage from the façade.

              All the relevant mechanisms and devices installed in KSO switchgear cells are grounded. The upper door where auxiliary circuit devices are installed is grounded with flexible wire. The lower part of the switchgear cell façade has a grounding clip, which is used to connect elements that must be temporarily grounded to the grounded case.

The switchgear cell frame is welded directly to grounded metal structures. Bus bars can be grounded in any switchgear cell with voltage transformer. Ground buses (conductors) are coated with black paint.

       The upper door of the switchgear cell serves as a panel for auxiliary circuit arrangement. The façade accommodates devices mainly with back-connected wiring (microprocessor units, protective relays, control and alarm relays, gages and meters).

Specification of switchgear cell KSO 285:

KSO switchgear cell parameters

Parameter value

Rated voltage of KSO switchgear cell, kV

6; 10

Maximum operating voltage of cells, kV

7.2; 12

Rated current of KSO switchgear cell primary circuits, А

400; 630; 1000

Rated current of KSO switchgear cell bus bars and busbar bridges, А

630; 1000

Rated current of high-voltage circuit breakers, А

630; 1000

Rated breaking current of high-voltage circuit breakers, kA

20

Rated voltage of auxiliary circuits, protection, control and alarm circuits, dc and ac voltage transformer circuit (protection, measurement, metering, automatic circuit breaker)

220

100

Rated current of current transformers, А

50; 75; 100; 150; 200; 300; 400; 600; 800; 1000

Current of electro-dynamic stability, kA

52

Thermal stability current, kA

20

Insulation according to GOST 1516.1-96

standard

KSO switchgear cell light circuits:                

- inside the cell                                                        

36 

- outside the cell

220

Dimensions of KSO switchgear cells (with bus bars): (height х width х depth)

2800х1000х1100

 

Electric schematic diagrams for KSO switchgear cells, 6 (10) kV:

схемы главных цепей камер КСО

Price for KSO Switchgear Cells, Series 200 in rubles, including an 18% VAT

1

KSO  285 -1 VV-600

180 500

2

KSO 285 -2 VV

193 900

3

 KSO 285 -3 VV

192 600

4

 KSO 285 -4 VV 600

185 200

5

 KSO 285 -5 VV 600

190 000

6

 KSO 285 -6 VV 600

194 400

7

 KSO 285 -7 VV 600

197 700

8

 KSO 285 -8 VV 600

223 700

9

KSO 285 -9-400

55 700

10

 KSO 285 -10-400

60 700

11

 KSO 285 -11-400

69 100

12

 KSO 285 -12-600

84 700

13

 KSO 285 -13-400

94 500

14

 KSO 285 -14-400

90 800

15

 KSO 285 -15-400

103 100

16

 KSO 285 -16-400

88 800

17

 KSO 285 -18-600

82 800

18

 KSO 285 -19-600

87 600

19

 KSO 285 -20-400

92 500

20

 KSO 285 -22-600

54 300

21

 KSO 285 -23-600

54 300

22

 KSO 285 -24-600

43 400

23

 KSO 285 -25-600

76 600

24

 KSO 285 -26-600

41 700

25

 KSO 285 -27-600 (reserve)

54 100

26

 KSO 285 -28

40 500

27

 KSO 285 -31

23 300

28

 KSO285 -32

24 400

To make an order, please, fill in the DATA SHEET for KSO Switchgear Cells, Series 200

Russian version of KSO Switchgear Cells, Series 200
Operating time: round the clock, every day
Phone in Ekaterinburg +7 (343) 310-04-40, Phone in Chelyabinsk +7 (351) 240 -02-84
Phone in Moscow +7 (495) 661-31-01, Phone in St.Petersburg +7 (812) 600-36-31
E-mail: uztt@mail.ru ICQ: 350 974 476 | 576 906 550
Rambler's Top100 Яндекс цитирования